SPECIALIZATION- Steel construction fire protection

     Our specialization of a few years’ is a fire and corrosion protection of steel constructions in building industry.

   Carbon steel is a very popular and willingly used construction material.
In contrast to the reinforced concrete, steel construction is getting hot very quickly and because of a decrease of the plasticity limit and springiness it is getting deformed. This process is started at temperature of 450-550° C.
This parameter is called steel critical temperature.
Just after the steel construction reaches this point it is getting deformed and damaged. This means the damage of the all supported construction and building collapse.

    To keep the stability and durability of the steel construction until the fire extinguish or building evacuation we need to perform fireproof protection of it. The goal is to achieve temperature insulation that in case of the open fire (temperature on the level of 800-1200°C) the steel construction is steel kept below the critical load-bearing capacity level for some time.
In accordance to the required period of time (at that period of time the construction is still stable) we may define different critical temperatures. If it is not unambiguously defined we usually assume:

- R15, R30 – 550°C
- R60 – 500°C
- R90, R120, R180, R240 – 450°C

We are ready to execute the following protection systems:


Spray system – VERMIPLASTER (PROTECCIÓN PASIVA 2000, S.L.).

The system is dedicated for fire protection class R30, R60, R90, R120 i R180.

    Vermiplaster it is a brand new system on the market of steel construction fireproof systems. Vermiplaster product is a low granulation, powdered mixture based on the calcium sulphurous.
Reduction of its weight is being achieved by the addition of self-expanding minerals. Its physical/chemical features are improved to achieve the optimal consistence during mixing, applying and hardening. It does not contain any toxic or dangerous chemicals. It produces a lot of water vapour while heated.

    Vermiplaster is applied mechanically, with a use of aggregate spraying machine which mixes it with water and pressurised air.
Vermiplaster can not be applied beyond critical temperatures (<5°C; >40° C) and must be protected against sunshine and strong wind while applied.
There is not recommended to use Vermiplaster on the open steel surfaces and in high humidity or condensate water conditions. It that case we recommend surface cleaning and surface protection against corrosion with a use of ground coating paint or waterproof paint.
In case of low level of humidity that is absorbed inside the building the system does not require any special treatment.

Vermiplaster is produced by PROTECCIÓN PASIVA 2000, S. L. in plant Dos Hermanas (Sewilla) Spain.
The production process is automated (automatic raw materials dosage system). It guarantees the stable characteristic of the final product.
The production process is continuously supervised in accordance with quality systems ISO9002 and ISO14001 (environment protection politics). The rules are approved by SGS and marked (010309/S.C. and 030070/MA).
Technical Approval No AT-15-6607/2005


Casing system CONLIT 150 (ROCKWOOL POLSKA Sp. z o.o.).
The system is dedicated for fire protection class R30, R60, R90, R120, R180 and R240.

    System COLINT 150 is dedicated for fireproof protections of the steel constructions inside the building (pillars and bar supports, beams) with a cross-section mass factor U/a ≤ 300-1.
The system consist plates and shape elements made of mineral wool (nominal density 165kg/m3) classified in class A1 as a non flammable product with a parching fibre temperature over 1000°C and special glue Conlit Glue. Additional assembling elements: pins, screws, nails.

There are three types of CONLIT plates:
- CONLIT 150 P – without upper aluminium layer;
- CONLIT 150 A/F – with aluminium upper layer;
- CONLIT 150 W/SCRIM – with glass fibber upper layer (special order).
Technical Approval No AT-15-3339/2005


Casing system PAROC FPS 14 (PAROC GROUP OY AB).

The system is dedicated for fire protection class R30, R60, R90, R120, R180 and R240.

    The system PAROC FPS 14 is dedicated for fireproof protection of steel construction inside the building with a cross-section mass factor U/a ≤ 300-1. The rectangular casings are fixed tightly (box method).
The system consist plates made of mineral wool (nominal density 140kg/m3) classified in class A1 as a non flammable product with a parching fibre temperature over 750° C and mechanical assembling elements: spiral screws, steel pins with self-tightening overlaps.
Technical Approval No AT-15-5489/2002


Casing System RIDURIT (RIGIPS POLSKA Stawiany, Sp. z o.o.).

The system is dedicated for fire protection class R30, R60, R90, R120, R180 and R240.

    The system RIDURIT is dedicated for fireproof protection of steel construction inside the building with a cross-section mass factor U/a ≤ 300-1. The rectangular casings are fixed tightly (box method).

System consist:
- plaster plates RIDURIT made by UK Company BPB GYPSUM Ltd.;
- zinc coated steel elements for RIDURIT plates fixing into the wall and ceiling;
- screws and staplers for cover assembling;
- putty mass RIDURIT for tightening of the plate joints.
Technical Approval AT-15-4148/00


Casing system FIREBOARD (KNAUF Sp. z o.o.).

The system is dedicated for fire protection class R30, R60, R90, R120, R180 and R240.

    The system FIREBOARD is dedicated for fireproof protection of steel construction inside the building with a cross-section mass factor U/a ≤ 300-1. The rectangular casings are fixed tightly (box method).

System consist:
- plaster plates FIREBOARD made by KNAUF WEST- DEUTSCHE GIPSWERKE thickness: 15mm, 20mm, 25mm, 30mm;
- zinc coated steel elements for plates fixing into the wall and ceiling;
- zinc coated steel profiles;
- zinc coated, steel fastening cramps;
- sheet metal fixing screws;
- steel, expanding screws;
- putty mass KNAUF FIREBOARD SPACHTEL for tightening of the plate joints.
Technical Approval AT-15-5792/2003


Casing system PROMATECT (PROMAT TOP Sp. z o.o.).

The system is dedicated for fire protection class R30, R60, R90, R120.

    The system PROMATECT is dedicated for fireproof protection of steel construction inside the building with a cross-section mass factor U/a ≤ 300-1.
System consists:
- fireproof silicate-concrete plates PROMATECT;
- fixing elements – staplers and screws.
Technical Approval AT-15-3855/99